Input Sensor Data
Chilled Water Inlet Temp (°C):
Chilled Water Outlet Temp (°C):
Chilled Water Flow (m³/hr):
Condenser Water Inlet Temp (°C):
Condenser Water Outlet Temp (°C):
Ambient/Wet Bulb Temp (°C):
Refrigerant Suction Pressure (bar):
Refrigerant Discharge Pressure (bar):
Discharge Temperature (°C):
Oil Pressure (bar):
Power Consumption (kW):
Rated TR:
Run Diagnostics
Legend:
Good
Average
Poor
Results
Enter values and click Diagnose.
Fault Detection Logic
Low Gas:
Low suction pressure + high discharge temp.
Condenser Issue:
High discharge pressure + high condenser ΔT.
Evaporator Flow Issue:
Small ΔT (<3°C) or high ΔT (>10°C).
High Approach:
Condenser Outlet Temp - Ambient Temp > 6°C.
Oil Pressure Issue:
Oil ΔP < 1 bar.
Overheating:
Discharge temp > 95°C.
Overload:
Actual TR > Rated TR.